EVT / PVT Ductwork Cleanliness Verification

    EVT / PVT Ductwork Cleanliness Verification

    Independent ventilation hygiene assessors · No cleaning services

    Last reviewed:

    The vacuum test measures how much dust is on a defined area of duct surface, by weight. It gives a gravimetric result in grams per square metre that can be compared with TR19 Air criteria, and it works on surfaces where deposit thickness testing is not reliable.

    Plan an EVT verification survey

    Established 19992,500+ assessmentsSafeContractor approvedBOHS Affiliate MemberLondon & South East

    EVT, PVT — what the names mean

    The test was originally called the Preferred Vacuum Test (PVT). Current guidance refers to it as the vacuum test, commonly written EVT. Both names describe the same approach: dust is drawn from a template area of duct surface onto a pre-weighed filter, and the filter is re-weighed to give the mass of dust per square metre.

    How EVT differs from DTT

    The two methods measure different things.

    EVT and DTT compared
    Vacuum test (EVT)Deposit Thickness Test (DTT)
    What it measuresMass of dust per area (g/m²)Thickness of dry deposit (microns)
    ResultAfter weighingOn site, immediately
    SurfacesWider range, including where DTT is unreliableSuitable flat, rigid metal surfaces
    Typical useQuantitative verification, pre- and post-cleanCondition surveys and pre/post-clean comparison

    Swipe sideways to see the full table →

    When EVT is used

    EVT is the right choice in several situations.

    • Pre-clean surveys where a gravimetric baseline is needed
    • Post-clean verification of cleaning works
    • Surfaces where DTT cannot give a reliable reading
    • Where a client, specification or insurer requires a gravimetric result
    • Disputed results, where an objective weighed measurement helps

    How an EVT survey works

    An EVT survey follows six steps.

    1. Agree purpose and scope

      We confirm whether the survey is pre-clean, post-clean or both, and which systems are included.

    2. Select sample locations

      We choose representative locations using the same principles as for DTT: system layout, air velocity, bends, filters, fan sections and visible condition.

    3. Take samples

      At each location a template is fixed to the duct surface and the dust within it is drawn onto a pre-weighed filter cassette.

    4. Record and track

      Each sample is labelled, photographed in place and recorded on a sample schedule so the chain from location to result is clear.

    5. Weigh and calculate

      Filters are re-weighed and the dust mass is converted to grams per square metre.

    6. Compare and report

      Results are compared with the TR19 Air criteria for the system and reported with conclusions and recommendations.

    Standard applied

    We sample and report in line with BESA TR19® Air (Version 2, 2026), and state the method and criteria used for each system in the report.

    What EVT cannot tell you

    • It does not identify what the dust is or whether it contains micro-organisms
    • It does not measure ventilation performance
    • It describes the sampled locations; unsampled and inaccessible sections are recorded, not assumed
    • Results are not available on site; they follow weighing

    What your EVT report includes

    • Purpose, scope and system boundaries
    • Sample location plan and schedule
    • Photographs of each sample location
    • Results in g/m² for each sample
    • Summary by system and comparison with TR19 Air criteria
    • Pre- and post-clean comparison where applicable
    • Limitations and inaccessible areas
    • Conclusions and recommended actions

    Plan an EVT verification survey

    Free, no-obligation — we typically respond within 2 hours.

    🔒 Your details are private and never shared with third parties.

    Frequently Asked Questions

    Yes. PVT (Preferred Vacuum Test) is the older name. Current guidance refers to the vacuum test, often written EVT. The method is the same.

    DTT is quick and gives results on site, but it only works reliably on suitable flat metal surfaces with dry deposits. EVT gives a weighed result and can be used where DTT cannot.

    Results follow weighing of the samples, so they are not instant. We agree the reporting timescale when we scope the survey.

    Yes. We do not provide cleaning, so our post-clean verification is fully independent of the contractor.